CONDITION | POSSIBLE CAUSES | SOLUTIONS |
OVERLOAD LED ON And POWER LED OFF | 1 .Short circuit at terminals 8 and 10 2.Short circuit at any of the loop detectors in the board 3.Short circuit in the control board | 1.Remove the short circuit condition at the terminals |
2.Remove the defective loop detector 3.Send the board to repair | ||
OVERLOAD LED ON And POWER LED ON | 1 .Excessive current draw at terminal 10 2.Over-voltage at the 120 VAC line input | 1 .Reduce the accessories load from terminal 10 2.Verify your electrical power |
SYSTEM ON LED FLASHING | 1 .One limit switch is faulty 2.Motor thermal fuse has popped-out | 1 .Test the limit switches and wire connections, fix the fault 2.Reset the motor |
REVERSE SENSOR LED ON | 1 .Gate has encountered and obstruction during traveling 2.Reverse sensor is extra sensitive | 1.Remove the obstruction |
2.Turn the reverse sensor switch counter clockwise a little more and try again | ||
ALARM SENSOR LED ON | 1 .Gate encountered an obstruction during traveling 2.Alarm sensor is extra sensitive | 1.Remove the obstruction |
2.Turn the alarm sensor switch counter clockwise a little more and try again | ||
ALARM SENSOR LED ON | 1 .Gate encountered and obstruction during traveling 2.Alarm sensor is extra sensitive | 1.Remove the obstruction |
2.Turn the alarm sensor switch counter clockwise a little more and try again | ||
COMMAND PROCESSED LED ON | 1 .There is a command hold active | 1 .This is a normal response of the gate operator. It does not represent necessarily that there is a problem. |
TIMER LED BLINKING And COMMAND PROCESSED LED BLINKING | 1.There is a command holding the gate open | 1. This is a normal response of the gate operator. It does not represent necessarily that there is a problem. Check inputs for command. |
TIMER LED BLINKING, COMMAND PROCESSED LED BLINKING And REVERSE SENSOR LED ON | 1 .Gate has reopened because it encountered an obstruction while closing. | 1 .Any renew command will resume normal operation. Check for obstructions. |
AUDIO ALARM ON | 1 .Gate has encountered two consecutive obstructions while trying to close or open | 1.Any renew command will resume normal operation but not a radio command. Check for obstructions. |
2.You can stop the alarm by using the stop button. | ||
ANY-LOOP LED ON And NO VEHICLE ON THE SENSING AREA | 1 .The loop detector needs to be reset. | 1.Reset the loop detector (If you use Elite Plug-in Loop detectors, change the setting for sensitivity and come back to your original setting). |
2.The wire loop has been disrupted | 2.Verify and correct connections | |
3.The loop detector needs to work in a different frequency | 3.Set a different working frequency | |
4.The loop detector is too sensitive | 4.Decrease the sensitivity of the loop detector |